This specification document covers the projection principles for antenna mounted monopole towers to be used in GSM base station installation projects
Bila ada konflik antara berbagai spesifikasi standar atau data desain teknik, spesifikasi standar yang paling ketat harus digunakan sebagai dasar setelah persetujuan.
If revisions to the relevant standards are to be published, it is the contractor's responsibility to comply with the new standards and update production to those standards after approval has been obtained
Sistem metrik akan digunakan dalam pengukuran.
3. Design principles
Kecuali diminta lain oleh pelanggan, menara akan dirancang sesuai dengan ketinggian berikut.
Unless otherwise requested by the customer, the tower will be designed according to the following heights.
Tiang tunggal dapat berupa sambungan slip poligonal atau pembuatan bergelang
Semua antena monopole harus memiliki aksesori untuk pemasangan antena, penahan kabel, tangga ke puncak struktur serta pagar pengaman dan gantungan, grounding, sistem konduktor petir dan sistem lampu peringatan pesawat.
Kontraktor harus merancang perhitungan, gambar garis, gambar fabrikasi dan perakitan, gambar fabrikasi dan bill of material sebelum pengiriman.
Itu harus dirancang untuk membuat operasi dan pemeliharaan mudah dilakukan.
Elemen struktural dan penghubung akan diberi dimensi sesuai dengan edisi terbaru Pedoman Desain Menara Transmisi Baja - ASCE yang dikeluarkan oleh American Society of Civil Engineers (ASCE).
Sebuah tangga akan dibangun di monopole untuk pemeliharaan dan operator untuk memanjat menara. Jarak anak tangga maksimal 30 cm. Pagar pengaman dan alat penahan jatuh harus disediakan untuk dipasang pada tangga akses.
Desain menara memungkinkan pemasangan lampu peringatan pesawat dan arester tembaga di titik tertinggi, dengan panjang minimal 1,2 meter. Lampu peringatan pesawat harus mudah diakses.
Kontraktor bertanggung jawab untuk memperoleh hasil dari desain menara, pengujian penerimaan dan jaminan kualitas untuk menunjukkan kepatuhan terhadap semua kondisi yang ditentukan dalam spesifikasi ini.
Kontraktor tidak boleh menggunakan monopole yang dirancang untuk tujuan lain tanpa persetujuan sebelumnya dari Klien.
Setiap monopole harus dirancang untuk berada dalam penampang melintang horizontal dodecagonal yang optimal-(karena goyang dan getaran harus dijaga seminimal mungkin) dan penyangga-diri, dihitung dari tegangan-kompresi sistem kekuatan.
Kehidupan monopole harus setidaknya 30 tahun.
5. Platform
Monopoles are available with or without top platform upon request and/or approval by Oman Mobile.
· The diameter of the top platform should be 3.0 m, and for monopole antennas without a top platform, a small shallow circular area should be provided for access to the antenna.
· Platforms should be fitted with non-slip floors, properly bolted to a suitable load bearing structure. Additionally, the platform floor must not allow tools and objects to fall.
· The top platform should be provided with footrests (h=15cm) and guard rails (made of two electric currents) with a height of not less than 110cm according to the current regulations.
· Work platforms should be accessed through hatches with opening and closing systems.
Lubang palka harus bisa tetap terbuka jika perlu.
Semua sambungan bawah tanah ke sistem pentanahan harus menggunakan metode Cadweld.
7. Elemen baja
Jika elemen penghubung memiliki flens, jumlah attachment dan eksentrisitas attachment dijaga serendah mungkin.
· Dimensioning of elements and connecting elements will be in accordance with the latest issue of Steel Transmission Tower Design Guidelines - ASCE published by the American Society of Civil Engineers - ASCE.
· The necessary holes for grounding must be designed.
· Monopolar connection and fixation: The monopolar base plate is fixed to the concrete base with anchor bolts and is properly grouted
· If required, the Contractor shall conduct his own on-site survey and shall be responsible for obtaining all dimensions and levels required to properly manufacture the steelworks.
· It is the contractor's responsibility to make each piece to the correct form and size.
· The Contractor shall notify the Engineer of the date of commencement of fabrication, shall keep the Engineer informed of the fabrication schedule, and shall allow the Engineer or his representative full access to his factory at all reasonable times to be at any stage of his fabrication. It must be clearly understood by the Contractor that any material and workmanship that does not conform to this specification, whether at his workplace, on site or at the installation location, shall be rejected and replaced to the full satisfaction of the Engineer.
8. Asumsi Beban Unipolar
Untuk desain monopole, beban berikut harus dipertimbangkan: Pembebanan Antena:
· N degree 6 mobile antennas, each weighing 15 Kg and measuring 2.58 x 0.3 x 0.15 m.
· N degree 2 solid parabolic antenna with an average weight of 25 Kg and a diameter of 0,6 m.
Antena parabola padat N derajat 2 dengan berat rata-rata 45 Kg dan diameter 1,2 m.
beban lainnya
Beban statis pada peralatan bantu seperti feeder, feeder joint, struktur antena dan peralatan instalasi lainnya.
Kecepatan angin:
· Design wind speed is 160 Km/h (45 m/s).
· The operating wind speed (at which maximum twist and tilt should be ±0.5 degrees) should be 120 Km/h (34 m/s).
10. Tangga dan Dudukan Kabel
tangga kabel vertikal
Tangga kabel vertikal dapat berupa braket eksternal pada tiang monopole yang dekat dengan tangga atau digunakan untuk menahan kabel di
Kait J-internal di dalam monopole.
11.
Tangga Masuk dan Sistem Perlindungan Jatuh Monopole harus dilengkapi dengan tangga galvanis celup panas dan sistem keselamatan yang disetujui. Sistem keselamatan harus mencakup arester jatuh (tikus) yang dapat bergerak bebas pada kabel baja atau lintasan yang sepenuhnya kontinu dan yang mengunci dirinya sendiri jika jatuh untuk melindungi individu agar tidak jatuh. Tangga harus memiliki lebar setidaknya 400mm. Jarak anak tangga (ketebalan minimum 16 mm) harus maksimum 250 mm dan harus mampu menahan beban terpusat sebesar 1 kN (gM=1.5). Seharusnya tidak ada hambatan pada kaki setelah menaiki tangga.
12. Fasteners
Baut, Mur dan Washer
Baut, mur, dan ring pemasangan harus memenuhi salah satu standar berikut (atau yang setara):